EESS

Under the latest MCS standards, particularly MCS 032:2025, there are specific guidelines regarding battery degradation when performing system performance calculations for Electrical Energy Storage Systems (EESS).([MCS][1])

šŸ”‹ Battery Degradation in Performance Calculations

While MIS 3012:2025 focuses on the installation aspects of battery storage systems, MCS 032:2025 provides detailed methodologies for estimating system performance, including considerations for battery degradation.

Key points include:

  • Cycle Limitations: To account for battery degradation over time, MCS limits the number of cycles assumed in annual energy discharge calculations to 2 cycles per day, totaling 730 cycles per year. This conservative approach ensures that performance estimates remain realistic over the system's lifespan. ([MCS][1])

  • Usable Capacity Allocation: When calculating performance, it's essential to determine the proportion of the battery's usable capacity allocated for self-consumption versus other services (e.g., backup power, grid services). The sum of these allocations should not exceed 100% of the total usable capacity. ([MCS][1])

  • Performance Estimates: Installers should provide clear documentation on how battery degradation impacts system performance over time, ensuring transparency with clients regarding expected energy savings and system efficiency.

šŸ“„ Documentation and Compliance

To remain compliant with MCS standards:

  • Performance Calculations: Ensure that all performance estimates incorporate the 730 cycles per year limitation and clearly outline assumptions made regarding battery degradation.([MCS][1])

  • Customer Communication: Provide clients with detailed explanations of how battery degradation may affect system performance, including any assumptions made in the calculations.

  • Record Keeping: Maintain thorough records of all calculations and justifications related to battery degradation for auditing purposes.([MCS][2])